20kV oil filled transformers

Description:

It can save the construction fee of the power system. It is the developing product of energy conservation in power systems.
Quote Now

[contact-form-7 id=”125″ title=”Contact Form”]

Description

Compared with the 10kV class, the 20kV three phase oil-immersed distribution transformer has some advantages:

  1. Increase power supply capability
  2. Ensure the voltage quality
  3. Debase the electric energy loss in the power system, etc.

It can save the construction fee of the power system. It is the developing product of energy conservation in power systems.

20kV oil filled transformer Specification

Rated current(A) Voltage combination and tap range link group No-load current(%) No-load loss of type 11

(W)

 load loss of type 13  (W) Type 11、13 load loss (W) short circuit impedance(%)
HV

(KV)

High voltage tap range % LV

(KV)

30 20

21

±2×2.5

±5

0.4 Dyn11

Yyn0

2.1 100 80 690/660 5.5
50 2 130 104 1010/960
63 1.9 150 120 1200/1150
80 1.8 180 144 1440/1370
100 1.6 200 160 1730/1650
125 1.5 240 192 2080/1980
160 1.4 290 232 2540/2420
200 1.3 340 272 3000/2860
250 1.2 400 320 3520/3350
315 1.1 480 384 4210/4010
400 1 570 456 4970/4730
500 1 680 544 5940/5660
630 0.9 810 648 6820  

 

 

6.0

800 0.8 980 784 8250
1000 0.7 1150 920 11330
1250 0.7 1380 1104 13200
1600 0.6 1660 1328 15950
2000 0.6 1950 1560 19140
2500 0.5 2340 1872 22220

You Also Like